Specializing in the production of electrical metering and protection equipment.

JSQ-110



Inquiry for a quote

Keywords:

Voltage transformer for GIS

Detailed Introduction

 

Product Description:

The 110 kV GIS Three-phase Voltage Transformer is an integrated, electromagnetic voltage transformer designed for 110 kV AC power‑system GIS equipment. It incorporates the A, B, and C phase voltage sensing units within a single metal‑sealed enclosure, which is filled with standard‑pressure SF₆ gas to provide insulation and heat dissipation. The device is reliably connected to the GIS three‑phase common busbar via dedicated basin‑type insulators, enabling simultaneous acquisition of three‑phase system voltage signals. It supplies precise three‑phase voltage data to substation protection, measurement, and metering devices, and is well suited to the compact arrangement of 110 kV three‑phase common‑busbar GIS systems. The product complies with standards such as GB/T 20840 and IEC 61869, offering advantages including high integration, reduced footprint, and robust reliability.

Product Features:

1. An innovative 110 kV three-phase integrated box-type structure, featuring a low overall height and compact footprint, significantly reducing installation space and land occupation compared to three separate single-phase units. 
2. The three-phase magnetic circuit and winding configuration are symmetrically designed, ensuring excellent phase‑to‑phase accuracy consistency and stable measurement errors, thereby meeting the requirements for high‑precision metering and fast relay protection. 
3. It employs a high-grade, low-loss silicon steel core, resulting in small excitation current, low no-load losses, excellent temperature-rise control, and stable performance under long-term full-load operation. 
4. Fully enclosed metal tank with an SF₆‑insulated internal structure, eliminating external porcelain bushings and completely preventing insulation failures such as pollution flashover, fog flashover, and condensation‑induced flashover. 
5. It features a built-in three-dimensional equal‑potential shielding structure, ensuring balanced electric field distribution across all three phases; its partial discharge level significantly exceeds the standard requirements, with no safety risks during operation. 
6. Exceptional sealing performance: the annual leakage rate of SF₆ gas is less than 0.1%, eliminating the need for routine maintenance and periodic gas replenishment, and resulting in extremely low lifecycle O&M workload. 
7. Strong resistance to system resonance and ferroresonance, with a dedicated detuning structure that effectively prevents voltage abnormalities and equipment damage. 
8. It exhibits excellent withstand capability against lightning surges, switching overvoltages, and short-duration power-frequency overvoltages, with ample insulation margin and high safety and reliability. 
9. The fully enclosed housing offers a high degree of protection, enabling reliable long-term operation in harsh environments such as high altitudes, severe pollution, high humidity, and coastal salt spray. 
10. The enclosure is corrosion‑resistant, wear‑resistant, and resistant to UV‑induced aging; it boasts high mechanical strength, and its seismic and impact‑resistance performance meets the transportation and operational standards of power systems.

Product Specifications

Model number

JDQXF-66

JSQ-66

JDQXF-110

JSQ-110

JDQXF-220

JDQXF-330

JDQXF-500

JDQXF-765

Maximum Equipment Voltage (kV)

72.5

126

252

363

550

800

Rated frequency (Hz)

50/60

Installation method

Upright/Inverted/Horizontal

Insulation type

SF6

SF6 or mixed gas

SF6

Rated voltage factor

1.2 times, consecutive

1.9 times, 8 hours

1.5 times, 30 seconds

Rated Power-Frequency Withstand Voltage (kV)

160

230

460

520

740

975

Rated Lightning Impulse Withstand Voltage (kV)

350

550

1050

1175

1675

2100

Secondary winding (1a–1n)

Accuracy level

Class 0.2, Class 0.5

Rated Output (VA)

50

100

50

Secondary winding (2a–2n)

Accuracy level

Class 0.5, Class 3P

Rated Output (VA)

50

100

50

Remaining winding (da-dn)

Accuracy level

3P level

Rated Output (VA)

300

SF6 rated pressure (20°C) (MPa)

0.5

0.4

SF6 recharging pressure (20°C) (MPa)

0.45

0.35

SF6 leakage rate (%)

<0.05%

SF6 trace moisture content (μL/L)

≤150

External dimensions

Height (mm)

792

1000

792

1000

1310

1545

1725

2395

Length (mm)

420

795

420

795

666

720

974

1358

Width (mm)

420

795

420

795

666

720

974

1358

Base mounting dimensions

Mounting hole (mm)

4×φ24

4×φ26

4×φ24

4×φ26

4×φ30

4×φ26

4×φ26

8×φ34

Hole spacing (mm)

330×330

550×550

330×330

550×550

560×560

590×590

700×700

480×680/

680×480

Total product weight (kg)

150

460

350

650

950

1800

Quotation Inquiry

Please provide your contact information and specify your requirements, and we will arrange for a dedicated representative to get in touch with you.

Submit

JSQ-110



Product Installation and User Manual Download:

Inquiry for a quote

Keywords:

Voltage transformer for GIS

Contact Information

Service Hotline:

+86-400-619-6979

Service email: tkhgqscb@163.com

Company Address: No. 11526, Longtan South Road, High-tech Zone, Tai’an City, Shandong Province

Looking forward to working with you.

Please let us know what product you need.