Specializing in the production of electrical metering and protection equipment.

LVQB-500



Inquiry for a quote

Keywords:

35–500 kV SF6 Gas-Insulated Current Transformer

Detailed Introduction

  • Science Fiction 6 Current transformer environmental parameters (customizable for extreme and high-altitude conditions):

Ambient temperature: maximum +40°C, minimum -30°C 
Altitude: ≤2000m 
Contamination Level: Class D/Class E Contamination 
Ice thickness: not exceeding 20 mm 
Maximum wind speed: not exceeding 35 m/s 
Intended use: Indoor or outdoor

  • Science Fiction 6 Current Transformer Product Structure

Science Fiction 6 Current Transformer (CT) Structure (from top to bottom)

1. Top: Housing + Primary Winding + Secondary Winding 
Enclosure: The enclosure completely isolates the internal secondary windings, bushing-type insulators, and other components from the external environment (including wind, rain, contamination, condensation, and small animals). 
Primary winding: The primary winding is typically a conductive rod that passes through the center of the secondary winding. 
Secondary winding: Used for metering, measurement, and protection purposes, it converts the primary high current into a secondary low current.
2. Middle section: Casing (external insulation) 
Casing: made of high-strength electrical porcelain or silicone rubber, serving as the primary external insulation, supporting the upper section, and sealing the internal cavity.
3. Bottom: Base + Secondary Junction Box 
Base: Supports the entire weight of the product and is equipped with mounting holes for connecting the product to the steel bracket.
4. SF 6 Gas (filling) 
Function: SF 6 As the primary insulating medium, gas offers an insulation strength far exceeding that of air and possesses self‑healing capabilities. It also enables oil‑free operation, thereby eliminating fire and explosion hazards, while simultaneously facilitating heat dissipation and protecting internal components from oxidation and moisture ingress. 
Requirement: SF 6 The gas shall have a high purity (≥99.9%), low water content (≤15 μL/L), and reliable sealing under rated pressure (annual leakage rate ≤0.5%). During operation, emissions are strictly prohibited to mitigate the greenhouse effect, and any decomposition products resulting from faults must remain within specified limits.
  • Science Fiction 6 Current transformer parameters (special parameters can be customized)

Project

LVQB-35

LVQB-110

LVQB-220

LVQB-330

LVQB-500

Product Type

Outdoor, single-phase, SF 6 Inverted position

Rated Voltage (kV)

35

110

220

330

500

Maximum Voltage (kV)

40.5

126

252

363

550

Rated frequency (Hz)

50

Rated primary current (A)

100-5000

100-5000

100-5000

0.5-5000

100-5000

Rated secondary current (A)

1/5

Instrument safety factor

5/10

Accuracy level

5P, 10P, 0.5, 0.5S, 0.2, 0.2S, TPY

Operating pressure (MPa)

0.4

0.45

Alarm pressure (MPa)

0.35

0.35

0.35

0.35

0.4

Short-term thermal current / Duration

40kA/3s

40kA/3s

50kA/3s

63kA/3s

63kA/3s

Rated dynamic stability current

100kA

100kA

125kA

160kA

160kA

Rated primary current amplification value

120%

Polarity

Negative polarity

Creepage distance (mm)

1256

3906

8593

11253

17050

Arc Flash Distance (mm)

500

1180

2200

3200

4200

1.2 µV/√3 partial discharge quantity (pC)

5

A partial discharge quantity (pc)

10

Insulating material

Porcelain

Porcelain / Silicone Rubber

Quotation Inquiry

Please provide your contact information and specify your requirements, and we will arrange for a dedicated representative to get in touch with you.

Submit

LVQB-500



Inquiry for a quote

Keywords:

35–500 kV SF6 Gas-Insulated Current Transformer

Contact Information

Service Hotline:

+86-400-619-6979

Service email: tkhgqscb@163.com

Company Address: No. 11526, Longtan South Road, High-tech Zone, Tai’an City, Shandong Province

Looking forward to working with you.

Please let us know what product you need.