News
-
-
-
-
Detailed Introduction
- Capacitive Voltage Transformer Replacement Parameters (customizable for extreme and high-altitude environments)
Ambient Temperature: Conventional products exhibit strong environmental adaptability, with an operating temperature range of -40°C to +40°C.
Altitude: ≤2500m
Contamination Level: Class D Contamination Conditions
Ice thickness: Can withstand ice accretion up to 20 mm.
Maximum wind speed: ≤35 m/s Maximum wind speed
Application: Meets the requirements of standard indoor and outdoor operation; for extremely demanding or specialized conditions, customized designs are available.
- Capacitive Voltage Transformer Parameters (Special Parameters Available for Customization)
Model number | TYD35/√3-0.01HF | TYD35/√3-0.02HF | TYD66/√3-0.01HF | TYD66/√3-0.02HF | TYD110/√3-0.01H | TYD110/√3-0.02H | TYD220/√3-0.005H | TYD220/√3-0.01H | TYD330/√3-0.005H | TYD500/√3-0.005H | TYD765/√3-0.005H | TYD1000/√3-0.005H | |
Maximum Equipment Voltage (kV) | 40.5 | 72.5 | 126 | 252 | 363 | 550 | 800 | 1100 | |||||
Rated Frequency (Hz) | 50/60 | ||||||||||||
Rated capacitance (pF) | 10000 | 20000 | 10000 | 20000 | 10000 | 20000 | 5000 | 10000 | 5000 | 5000 | 5000 | 5000 | |
Rated Voltage Factor/Time | 1.2/Continuous | ||||||||||||
1.9/8h | 1.5/30s | ||||||||||||
Rated Power-Frequency Withstand Voltage (kV) | 95 | 95 | 160 | 160 | 230 | 230 | 460 | 460 | 510 | 740 | 975 | 1200 | |
Rated Lightning Impulse Withstand Voltage (kV) | 200 | 200 | 350 | 350 | 550 | 550 | 1050 | 1050 | 1175 | 1675 | 2100 | 2400 | |
Rated switching impulse withstand voltage (kV) | / | 950 | 1300 | 1550 | 1800 | ||||||||
Partial discharge quantity (pC) under 1.2 µm/√3 | ≤5 | ||||||||||||
Secondary winding (1a1n) | Accuracy class | Class 0.2, Class 0.5 | |||||||||||
Rated Output (VA) | ≤20 | ≤50 | ≤30 | ≤50 | ≤30 | ≤100 | ≤30 | ≤100 | ≤30 | ≤50 | ≤50 | ≤15 | |
Secondary winding (2a2n) | Accuracy class | Class 0.5, Class 3P | |||||||||||
Rated Output (VA) | ≤30 | ≤50 | ≤30 | ≤50 | ≤30 | ≤100 | ≤30 | ≤100 | ≤50 | ≤50 | ≤50 | ≤20 | |
Secondary winding (3a3n) | Accuracy class | / | Class 0.5, Class 3P | ||||||||||
Rated Output (VA) | / | / | / | / | ≤30 | ≤100 | ≤30 | ≤100 | ≤50 | ≤50 | ≤50 | ≤20 | |
Secondary winding (dadn) | Accuracy class | 3P level, 6P level | |||||||||||
Rated Output (VA) | ≤100 | ||||||||||||
Product appearance and installation dimensions | Subject to the confirmed drawings. | ||||||||||||
Total product weight (kg) | 450 | 450 | 480 | 540 | 460 | 640 | 660 | 940 | 1150 | 1500 | 3400 | 7000 | |
Quotation Inquiry
Please provide your contact information and specify your requirements, and we will arrange for a dedicated representative to get in touch with you.
TYD-765
Product Installation and User Manual Download:
Keywords:
35–1000 kV Capacitive Voltage Transformer
Contact Information
Service Hotline:
Service email: tkhgqscb@163.com
Company Address: No. 11526, Longtan South Road, High-tech Zone, Tai’an City, Shandong Province
Looking forward to working with you.
Please let us know what product you need.
Specializing in the production of electrical metering and protection equipment.
WeChat Official Account
Contact Us
Service Hotline:
Service email: tkhgqscb@163.com
Company Address: No. 11526, Longtan South Road, High-tech Zone, Tai’an City, Shandong Province