Specializing in the production of electrical metering and protection equipment.

Y10WF-204-532 220kV



Inquiry for a quote

Keywords:

GIS surge arrester

Detailed Introduction

 

Product Features:

1. A newly designed 220 kV single-phase miniaturized GIS surge arrester, with an overall height of 1.365 m and a weight of 178 kg, is at an internationally advanced and domestically leading level. 
2. It employs high‑gradient zinc oxide varistors and a single‑column, multi‑section cage‑type core structure, delivering excellent volt‑ampere characteristics, low residual voltage, and ample protection margin, thereby precisely limiting various overvoltages. 
3. All-metal sealed tank structure, with internal insulation using SF₆ gas, no exposed porcelain bushings, resistant to pollution flashover and condensation, and suitable for complex insulation environments. 
4. Featuring an integrated design, the unit boasts a compact structure and small footprint, enabling seamless integration with GIS equipment and minimizing installation space requirements. 
5. Equipped with a built-in precision equalizing shield structure, it ensures uniform electric field distribution, minimal partial discharge, high operational stability, and reduced risk of failure. 
6. Excellent sealing performance, with an extremely low annual leakage rate of SF₆ gas (typically <0.1%), eliminating the need for routine gas replenishment and minimizing maintenance workload. 
7. It exhibits strong resistance to lightning overvoltages and switching overvoltages, boasts a large current-carrying capacity, offers excellent aging resistance and long service life, and meets the requirements for long-term stable operation. 
8. The all‑metal enclosure is fully sealed, ensuring reliable performance in harsh environments such as high altitudes, salt spray, dust, and humid heat, making it suitable for a wide range of applications. 
9. Under normal operating conditions, the leakage current is extremely low; it is passive and inductive‑free, with no reverse current and no risk of power‑frequency reverse‑current breakdown, ensuring high operational safety. 
10. It can be equipped with an online monitoring interface, supporting real-time monitoring of SF₆ pressure and arrester leakage current, thereby enabling intelligent operation and maintenance. 
11. The enclosure is made of corrosion- and rust-resistant materials, with a specially treated surface that provides excellent resistance to corrosion and abrasion, making it suitable for long-term outdoor installation.

Product Specifications

Product modelY10WF-102/266SY10WF-204/532Y10WF-300/727Y20WF-420/1046
System rated voltage kV r.m.s.110220330500
Maximum system voltage kV r.m.s.126252363550
Arrester rated frequency, Hz50
Installation methodUpright/Inverted
Insulating mediumSF6 or mixed gasSF6
Arrester rated voltage (Ur) kV r.m.s.102204300420
Nominal discharge current kA1020
Arrester continuous operating voltage (UC), kV r.m.s.79.6159228318
DC 1 mA reference voltage kV148296425565
Power-frequency (resistive 1 mA) reference voltage ≥ kV (peak/√2)102204300420
Residual Voltage Test1/5 μs steep‑wave impulse residual voltage ≤ kV P2975948141170
8/20 μs lightning impulse residual voltage ≤ kV P2665327271046
30/60 μs switching impulse residual voltage ≤ kV P226452618858
Repetitive charge transfer C1.21.62.83.6
4/10 Withstand 2 large-current surges, kA100
Leakage current at 0.75 times the DC 1 mA reference voltage ≤ μA3050
Continuous currentTotal current ≤ 900 μArmsTotal current ≤ 2000 μArmsTotal current ≤ 5000 μArms
Resistive current ≤ 250 μA pResistive current ≤ 1000 μA pResistive current ≤ 1500 μA p
1.1 Partial discharge quantity under UC ≤ pC5
SF6 rated pressure (20°C) (MPa)0.5
SF6 recharging pressure (20°C) (MPa)0.45
SF6 leakage rate (%)<0.05%
SF6 trace moisture content (μL/L)≤150
External dimensionsHeight (mm)870143017802048
Length (mm)665520720795
Width (mm)665520720795
Base mounting dimensionsMounting hole (mm)4×φ284×φ294×φ304×φ28
Hole spacing (mm)550×550450×450620×620700×700
Total product weight (kg)225178330460

Quotation Inquiry

Please provide your contact information and specify your requirements, and we will arrange for a dedicated representative to get in touch with you.

Submit

Y10WF-204-532 220kV



Product Installation and User Manual Download:

Inquiry for a quote

Keywords:

GIS surge arrester

Contact Information

Service Hotline:

+86-400-619-6979

Service email: tkhgqscb@163.com

Company Address: No. 11526, Longtan South Road, High-tech Zone, Tai’an City, Shandong Province

Looking forward to working with you.

Please let us know what product you need.